WP_Post Object ( [ID] => 10060 [post_author] => 7 [post_date] => 2020-05-20 18:13:04 [post_date_gmt] => 2020-05-20 14:13:04 [post_content] => [post_title] => МС322-220 Модуль контроля и управления 4-х канальный [post_excerpt] => [post_status] => publish [comment_status] => closed [ping_status] => closed [post_password] => [post_name] => ms322-220-modul-kontrolya-i-upravleniya-4-h-kanalnyj [to_ping] => [pinged] => [post_modified] => 2020-08-10 18:06:06 [post_modified_gmt] => 2020-08-10 14:06:06 [post_content_filtered] => [post_parent] => 0 [guid] => http://plazma-t.ru/?post_type=device&p=10060 [menu_order] => 0 [post_type] => device [post_mime_type] => [comment_count] => 0 [filter] => raw ) Array ( [_edit_lock] => Array ( [0] => 1597128992:147 ) [_edit_last] => Array ( [0] => 7 ) [slide_template] => Array ( [0] => default ) [type_pr] => Array ( [0] => 0 ) [_type_pr] => Array ( [0] => field_5dfb521bfd66b ) [short] => Array ( [0] => МС322-220 ) [description] => Array ( [0] =>   Модуль МС322-220 применяется в системах пожарной сигнализации и предназначен для:
  • контроля двух сигнальных входов (занимают два адреса) и двух технологических входов (не имеют адреса) для подключения нормально-замкнутых и/или нормально-разомкнутых контактов типа «сухой контакт» с контролем исправности входов
  • управления двумя нереверсивными устройствами или одним реверсивным устройством напряжением питания 220В АС по командам от прибора ПАС300 с контролем исправности цепей управления на обрыв во всех состояниях и на КЗ в дежурном режиме
МС322-220 имеет встроенные трехцветные светодиодные индикаторы для расширенного отображения состояния всех входов, устройств, а также самого модуля. МС322-220 позволяет управлять режимом работы световых табло по алгоритму:
  • Дежурный режим – горит непрерывно;
  • Режим Пожар – мигает с программируемой длительностью
  Основные функции: Модуль обеспечивает:
  • Подключение и контроль состояния двух сигнальных нормально-замкнутых и/или нормально-разомкнутых входа типа «сухой контакт» с контролем исправности на обрыв и короткое замыкание и их передачу на прибор ПАС300. Для входов предусмотрена возможность программирования типа сигнала (Пожар, Внимание, Авария, нет сигнала), который будет формироваться в системе С300 при срабатывании входа. Каждый сигнальный вход имеет адрес и может быть установлен в любую из 40 зон контроля в ПАС300 (по умолчанию зона 1).
  • Подключение и контроль состояния двух технологических нормально-замкнутых и/или нормально-разомкнутых входа типа «сухой контакт» с контролем исправности на обрыв и короткое замыкание и их передачу на прибор ПАС300. Для входов предусмотрена возможность программирования назначения (Авария источника питания, Авария устройства, Автоматика отключена, Ручной Пуск), который будет формировать соответствующий сигнал в системе С300 при срабатывании входа. Технологические входы не имеют адреса, а привязаны к адресу соответствующего устройства или блок питания.
  • подключение двух нереверсивных исполнительных устройств или одного реверсивного устройства напряжением питания 220В АС с контролем исправности цепей управления на обрыв во всех режимах и короткое замыкание в дежурном режиме
  • встроенную защиту от короткого замыкания (плавкий предохранитель), рассчитанную на ток 3,0 А.
Полный контроль работоспособности обеспечивается как на физическом уровне (функция самотестирования в модуле), так и на программном уровне (постоянный опрос ПАС300) Модуль занимает 4 адреса в адресном пространстве С300. Интерфейсная часть МС322-220 питается от прибора ПАС300 Электронное программирование адреса (0 – заводская установка)   Восемь встроенных трехцветных светодиодных индикаторов обеспечивают расширенную индикацию как состояний самого модуля (неисправность, дублирование адресов, нулевой адрес, нет в базе ПАС300 и т.д.) помимо состояний Сработка и Дежурный режим, так и состояний подключенного оборудования, что значительно упрощает процессы настройки и обслуживания системы С300 в целом Для каждого нереверсивного устройства помимо включения/отключения и возможности задания задержки пуска и остановки, предусмотрена возможность контролировать выход устройства на режим (поле Адрес подтверждающего датчика), а также опции по контролю цепи управления устройства (контроль на обрыв, контроль на КЗ, контроль на обрыв и КЗ, не контролировать) и состояние выхода в дежурном режиме:
  • Опция «Инверсный выход» не активна - выход выключен;
  • Опция «Инверсный выход» активна - выход включен
) [advdesc] => Array ( [0] =>   Для реверсивного устройства помимо возможности задания задержки пуска и остановки предусмотрена возможность выбора дежурного состояния (Реверсивный нормально открытый, Реверсивный нормально закрытый), а также опции по контролю цепи управления устройства (контроль на обрыв, контроль на КЗ, контроль на обрыв и КЗ, не контролировать).   Для каждого устройства можно запрограммировать следующие команды:
  • «Пуск», «ПускУ12» - включение устройства по истечении времени задержки на пуск
  • «½ Пуск» - включение устройства при поступлении двух и более команд «½ Пуск»
  • «Пуск с блокировкой» - включение устройства, если отсутствует сигнал блокировки
  • «Стоп» - выключение устройства по истечении времени задержки на останов
  • «½ Стоп» - выключение устройства при поступлении двух и более команд «½ Стоп»
  • «Отключить автоматику» - перевод устройства в режим «Автоматика устройства отключена»
  • «Включить автоматику» - отключение режима «Автоматика устройства отключена»
В качестве условий для формирования команд может использоваться срабатывание:
  • В любой из 40 зон данного ПАС300 или любого из 24 приборов ПАС300, объединённых в сеть
  • Любого шлейфа любого из приборов управления ПУ/ПУМ/ПУ-PL, объединённых в сеть
  • В любой из 64 групп ЦПИ, в каждую из которых можно добавлять зоны ПАС и/или шлейфы ПУ/ПУМ/ПУ-PL
) [tth] => Array ( [0] => ) [_pods_razdel] => Array ( [0] => 12 ) [numorder] => Array ( [0] => 5 ) [tth_tabl] => Array ( [0] =>

Основные технические характеристики

Сигнальные входы Количество 2
Напряжение входов 3,3 В
Контроль исправности на обрыв и короткое замыкание
Максимальная длина линии 100 м
Назначение входов формирование сигналов: - сигнализации (Пожар, Внимание, Авария) - управления (Управление1, Управление2)
Тенхнологи-ческие входы Количество 2
Напряжение входов 3,3 В
Контроль исправности на обрыв и короткое замыкание
Максимальная длина линии 100 м
Назначение входов - авария питания; - авария устройства 1 или 2; - вкл/откл автоматику устройства 1 или 2; - ручной пуск/стоп устройства 1 или 2.
Устройства Количество управляемых устройств 2 независимых или 1 реверсивное
Напряжение для устройств равно напряжению электропитания модуля
Ток контроля нагрузки 1 мА
Максимальная мощность каждого выхода 100 ВА
Контроль исправности цепей на обрыв во всех состояниях и КЗ в дежурн. режиме
Ток контроля исправности цепей не более 1,0 мА
Сопротивление цепи управления не более 300 Ом
Электропитание модуля 2 входа: ≈ 170 ÷ 245 В, 50/60 Гц, не более 2 ВА (собственное потребление модуля)
Интерфейс С300 Электропитание интерфейсной части от ПАС300 по интерфейсу С300
Напряжение интерфейса С300 от 11,5 до 28,0 В
Количество адресов в протоколе С300 4
Потребляемый ток от интерфейса не более 1,0 мА
Гальваническая развязка интерфейса eсть
Изолятор короткого замыкания есть
Корпус Цвет корпуса светло-серый (RAL9002)
Масса не более 190 г
Габариты (ШхВхГ) 156х107х33 мм
Степень защиты оболочкой IP20
Крепление На саморезы или на DIN-рейку
Диапазон рабочих температур от минус 20 до +60°С
Допустимая относительная влажность до 93% при +40°С
Температура транспортировки и хранения от минус 50 до +50°С
Средний срок службы не менее 10 лет
Датчик вскрытия корпуса есть
) [hide_tech] => Array ( [0] => 0 ) [hide_down] => Array ( [0] => 0 ) [razdel_adr] => Array ( [0] => device ) [contact_form_code] => Array ( [0] => ) [_pods_devicedocs] => Array ( [0] => a:11:{i:0;i:10153;i:1;i:10154;i:2;i:3697;i:3;i:7592;i:4;i:7854;i:5;i:7527;i:6;i:8922;i:7;i:10165;i:8;i:3245;i:9;i:3308;i:10;i:9696;} ) [_pods_images] => Array ( [0] => a:1:{i:0;i:10529;} ) [_relevanssi_pin] => Array ( [0] => ) [_relevanssi_unpin] => Array ( [0] => ) [razdel] => Array ( [0] => 12 ) [images] => Array ( [0] => 10529 ) [devicedocs] => Array ( [0] => 10153 [1] => 10154 [2] => 3697 [3] => 7592 [4] => 7854 [5] => 7527 [6] => 8922 [7] => 10165 [8] => 3245 [9] => 3308 [10] => 9696 ) )


смотреть все изображения

МС322-220
МС322-220 Модуль контроля и управления 4-х канальный

 

Модуль МС322-220 применяется в системах пожарной сигнализации и предназначен для:

  • контроля двух сигнальных входов (занимают два адреса) и двух технологических входов (не имеют адреса) для подключения нормально-замкнутых и/или нормально-разомкнутых контактов типа «сухой контакт» с контролем исправности входов
  • управления двумя нереверсивными устройствами или одним реверсивным устройством напряжением питания 220В АС по командам от прибора ПАС300 с контролем исправности цепей управления на обрыв во всех состояниях и на КЗ в дежурном режиме

МС322-220 имеет встроенные трехцветные светодиодные индикаторы для расширенного отображения состояния всех входов, устройств, а также самого модуля.

МС322-220 позволяет управлять режимом работы световых табло по алгоритму:

  • Дежурный режим – горит непрерывно;
  • Режим Пожар – мигает с программируемой длительностью

 

Основные функции:

Модуль обеспечивает:

  • Подключение и контроль состояния двух сигнальных нормально-замкнутых и/или нормально-разомкнутых входа типа «сухой контакт» с контролем исправности на обрыв и короткое замыкание и их передачу на прибор ПАС300. Для входов предусмотрена возможность программирования типа сигнала (Пожар, Внимание, Авария, нет сигнала), который будет формироваться в системе С300 при срабатывании входа. Каждый сигнальный вход имеет адрес и может быть установлен в любую из 40 зон контроля в ПАС300 (по умолчанию зона 1).
  • Подключение и контроль состояния двух технологических нормально-замкнутых и/или нормально-разомкнутых входа типа «сухой контакт» с контролем исправности на обрыв и короткое замыкание и их передачу на прибор ПАС300. Для входов предусмотрена возможность программирования назначения (Авария источника питания, Авария устройства, Автоматика отключена, Ручной Пуск), который будет формировать соответствующий сигнал в системе С300 при срабатывании входа. Технологические входы не имеют адреса, а привязаны к адресу соответствующего устройства или блок питания.
  • подключение двух нереверсивных исполнительных устройств или одного реверсивного устройства напряжением питания 220В АС с контролем исправности цепей управления на обрыв во всех режимах и короткое замыкание в дежурном режиме
  • встроенную защиту от короткого замыкания (плавкий предохранитель), рассчитанную на ток 3,0 А.

Полный контроль работоспособности обеспечивается как на физическом уровне (функция самотестирования в модуле), так и на программном уровне (постоянный опрос ПАС300)

Модуль занимает 4 адреса в адресном пространстве С300. Интерфейсная часть МС322-220 питается от прибора ПАС300

Электронное программирование адреса (0 – заводская установка)

 

Восемь встроенных трехцветных светодиодных индикаторов обеспечивают расширенную индикацию как состояний самого модуля (неисправность, дублирование адресов, нулевой адрес, нет в базе ПАС300 и т.д.) помимо состояний Сработка и Дежурный режим, так и состояний подключенного оборудования, что значительно упрощает процессы настройки и обслуживания системы С300 в целом

Для каждого нереверсивного устройства помимо включения/отключения и возможности задания задержки пуска и остановки, предусмотрена возможность контролировать выход устройства на режим (поле Адрес подтверждающего датчика), а также опции по контролю цепи управления устройства (контроль на обрыв, контроль на КЗ, контроль на обрыв и КЗ, не контролировать) и состояние выхода в дежурном режиме:

  • Опция «Инверсный выход» не активна - выход выключен;
  • Опция «Инверсный выход» активна - выход включен
Подробнее

 

Для реверсивного устройства помимо возможности задания задержки пуска и остановки предусмотрена возможность выбора дежурного состояния (Реверсивный нормально открытый, Реверсивный нормально закрытый), а также опции по контролю цепи управления устройства (контроль на обрыв, контроль на КЗ, контроль на обрыв и КЗ, не контролировать).

 

Для каждого устройства можно запрограммировать следующие команды:

  • «Пуск», «ПускУ12» - включение устройства по истечении времени задержки на пуск
  • «½ Пуск» - включение устройства при поступлении двух и более команд «½ Пуск»
  • «Пуск с блокировкой» - включение устройства, если отсутствует сигнал блокировки
  • «Стоп» - выключение устройства по истечении времени задержки на останов
  • «½ Стоп» - выключение устройства при поступлении двух и более команд «½ Стоп»
  • «Отключить автоматику» - перевод устройства в режим «Автоматика устройства отключена»
  • «Включить автоматику» - отключение режима «Автоматика устройства отключена»

В качестве условий для формирования команд может использоваться срабатывание:

  • В любой из 40 зон данного ПАС300 или любого из 24 приборов ПАС300, объединённых в сеть
  • Любого шлейфа любого из приборов управления ПУ/ПУМ/ПУ-PL, объединённых в сеть
  • В любой из 64 групп ЦПИ, в каждую из которых можно добавлять зоны ПАС и/или шлейфы ПУ/ПУМ/ПУ-PL

Основные технические характеристики

Сигнальные

входы

Количество 2
Напряжение входов 3,3 В
Контроль исправности на обрыв и короткое замыкание
Максимальная длина линии 100 м
Назначение входов формирование сигналов:

- сигнализации (Пожар, Внимание, Авария)

- управления (Управление1, Управление2)

Тенхнологи-ческие входы Количество 2
Напряжение входов 3,3 В
Контроль исправности на обрыв и короткое замыкание
Максимальная длина линии 100 м
Назначение входов - авария питания;

- авария устройства 1 или 2;

- вкл/откл автоматику устройства 1 или 2;

- ручной пуск/стоп устройства 1 или 2.

Устройства Количество управляемых устройств 2 независимых или 1 реверсивное
Напряжение для устройств равно напряжению электропитания модуля
Ток контроля нагрузки 1 мА
Максимальная мощность каждого выхода 100 ВА
Контроль исправности цепей на обрыв во всех состояниях и КЗ в дежурн. режиме
Ток контроля исправности цепей не более 1,0 мА
Сопротивление цепи управления не более 300 Ом
Электропитание модуля 2 входа: ≈ 170 ÷ 245 В, 50/60 Гц,

не более 2 ВА (собственное потребление модуля)

Интерфейс С300 Электропитание интерфейсной части от ПАС300 по интерфейсу С300
Напряжение интерфейса С300 от 11,5 до 28,0 В
Количество адресов в протоколе С300 4
Потребляемый ток от интерфейса не более 1,0 мА
Гальваническая развязка интерфейса eсть
Изолятор короткого замыкания есть
Корпус Цвет корпуса светло-серый (RAL9002)
Масса не более 190 г
Габариты (ШхВхГ) 156х107х33 мм
Степень защиты оболочкой IP20
Крепление На саморезы или на DIN-рейку
Диапазон рабочих температур от минус 20 до +60°С
Допустимая относительная влажность до 93% при +40°С
Температура транспортировки и хранения от минус 50 до +50°С
Средний срок службы не менее 10 лет
Датчик вскрытия корпуса есть