Пороговый модуль контроля термокабеля МТС-х

WP_Post Object ( [ID] => 6227 [post_author] => 7 [post_date] => 2017-02-02 15:53:31 [post_date_gmt] => 2017-02-02 11:53:31 [post_content] => [post_title] => Пороговый модуль контроля термокабеля МТС-х [post_excerpt] => [post_status] => publish [comment_status] => closed [ping_status] => closed [post_password] => [post_name] => porogovyiy-modul-kontrolya-termokabelya-mts-h [to_ping] => [pinged] => [post_modified] => 2021-06-02 18:41:23 [post_modified_gmt] => 2021-06-02 14:41:23 [post_content_filtered] => [post_parent] => 0 [guid] => http://plazma-t.ru/?post_type=device&p=6227 [menu_order] => 0 [post_type] => device [post_mime_type] => [comment_count] => 0 [filter] => raw ) Array ( [_edit_lock] => Array ( [0] => 1622644760:116 ) [_edit_last] => Array ( [0] => 116 ) [short] => Array ( [0] => МТС-х ) [description] => Array ( [0] => Модуль МТС-х предназначен для контроля состояния извещателей пожарных тепловых линейных (термокабелей) и выдачи сигналов об их состоянии во внешние цепи. Модуль МТС-x поддерживает следующие типы термокабелей: - ГРИФ-термокабель (Эрвист) - рекомендуется, - ИП104 (GTSW) (Спецприбор), - PHSC (Protectowire), - LHD (Thermocable), - любой термокабель с удельным сопротивлением 0,05÷0,70 Ом/м. Область применения МТС-х может быть расширена для обнаружения возгорания во взрывоопасных зонах. В этом случае необходимо применять ИПТЛ-xxxС-ЕХ-ГРИФ-термокабель (xxxC –температура срабатывания) с оболочкой EX. Подключать термокабель необходимо через барьер искрозащиты ШСБ-ТК, устанавливаемый за пределами взрывоопасной зоны. Модули МТС-х разработаны таким образом, что не требуют никакой настройки при запуске системы. ) [advdesc] => Array ( [0] =>
  • В линейке пороговых модулей МТС-x предусмотрено три исполнения: - МТС-1 – с возможностью подключения одного термошлейфа; - МТС-2 – с возможностью подключения двух термошлейфов; - МТС-3 – с возможностью подключения трех термошлейфов.
 
  • В зависимости от внешней оболочки применяемого термокабеля МТС-x может контролировать возгорание практически в любых условиях эксплуатации: - для уличного и внутреннего применения в обычных условиях эксплуатации при применении термокабеля с оболочкой из ПВХ, например, ИПТЛ-xxxС-PVC-ГРИФ-термокабель (где xxxС –температура срабатывания); - с агрессивной внешней средой и в условиях сурового климата при применении термокабеля с оболочкой из фторполимера, например, ИПТЛ-xxxС-CR-ГРИФ-термокабель (где xxxС –температура срабатывания); - во взрывоопасных зонах и на объектах с высокими электромагнитными помехами при применении термокабеля со специальной экранированной оболочкой, например, ИПТЛ-xxxС-EX-ГРИФ-термокабель (где xxxС –температура срабатывания).
 
  • Модули МТС-х рассчитаны на установку в необслуживаемых помещениях: степень защиты оболочки IP65 и рабочий диапазон температур -40°С до +55°C.
  • Возможность подключить к модулю МТС-х двухпороговые тепловые линейные пожарные извещатели позволяет существенно снизить риск запуска систем противопожарной защиты объекта вследствие повреждения (короткого замыкания) термокабеля.
  • Модули обеспечивают наглядную информацию о состоянии термошлейфов и самого прибора при помощи трёхцветных индикаторов.
  • Не требуют настройки и программирования.
) [tth] => Array ( [0] => ) [_pods_razdel] => Array ( [0] => 1 ) [numorder] => Array ( [0] => 59 ) [tth_tabl] => Array ( [0] =>
Технические характеристики МТС-1 МТС-2 МТС-3
Количество термошлейфов 1 2 3
Допустимое удельное сопротивление термокабеля 0,05÷0,70 Ом/м
Длина термошлейфа 0÷3000 м (при 0,656 Ом/м) 0÷10000 м (при 0,19 Ом/м)
Сопротивление подводящих проводов не более 300 Ом
Контроль исправности шлейфов короткое замыкание / обрыв
Напряжение/ток питания шлейфов, не более 5,0 В/1,5 мА
Контроль вскрытия корпуса +
Выходы Пожар*, «сухой» перекидной контакт 1 2 3
Выход Авария*, «сухой» перекидной контакт +
Световая сигнализация Авария +
Питание +
Шлейф 1 + + +
Шлейф 2 - + +
Шлейф 3 - - +
Электропитание (≤ 2,0 Вт) =11÷30,5 В
Средний срок службы не менее 10 лет
Диапазон рабочих температур от -40°C до +55°C
Допустимая относительная влажность до 93% при 40°C
Степень защиты оболочки IP65
Климатическое исполнение УХЛ 3.1
Масса не более 0,5 кг
Габариты, мм (ширина х высота х глубина) 160х160х60
* 125 VAC/0,5 A; 24 VDC/1 A
) [hide_tech] => Array ( [0] => 0 ) [hide_down] => Array ( [0] => 0 ) [razdel_adr] => Array ( [0] => device ) [_pods_devicedocs] => Array ( [0] => a:16:{i:0;i:3245;i:1;i:3308;i:2;i:3307;i:3;i:2640;i:4;i:6237;i:5;i:6239;i:6;i:6352;i:7;i:7527;i:8;i:3697;i:9;i:8809;i:10;i:8922;i:11;i:10169;i:12;i:10715;i:13;i:10753;i:14;i:11737;i:15;i:11752;} ) [_pods_images] => Array ( [0] => a:2:{i:0;i:8857;i:1;i:8858;} ) [type_pr] => Array ( [0] => 0 ) [_type_pr] => Array ( [0] => field_5dfb521bfd66b ) [slide_template] => Array ( [0] => default ) [contact_form_code] => Array ( [0] => ) [_relevanssi_pin] => Array ( [0] => ) [_relevanssi_unpin] => Array ( [0] => ) [razdel] => Array ( [0] => 1 ) [images] => Array ( [0] => 8857 [1] => 8858 ) [devicedocs] => Array ( [0] => 3245 [1] => 3308 [2] => 3307 [3] => 2640 [4] => 6237 [5] => 6239 [6] => 6352 [7] => 7527 [8] => 3697 [9] => 8809 [10] => 8922 [11] => 10169 [12] => 10715 [13] => 10753 [14] => 11737 [15] => 11752 ) )


смотреть все изображения

МТС-х
Пороговый модуль контроля термокабеля МТС-х

Модуль МТС-х предназначен для контроля состояния извещателей пожарных тепловых линейных (термокабелей) и выдачи сигналов об их состоянии во внешние цепи.

Модуль МТС-x поддерживает следующие типы термокабелей:
– ГРИФ-термокабель (Эрвист) – рекомендуется,
– ИП104 (GTSW) (Спецприбор),
– PHSC (Protectowire),
– LHD (Thermocable),
– любой термокабель с удельным сопротивлением 0,05÷0,70 Ом/м.

Область применения МТС-х может быть расширена для обнаружения возгорания во взрывоопасных зонах. В этом случае необходимо применять ИПТЛ-xxxС-ЕХ-ГРИФ-термокабель (xxxC –температура срабатывания) с оболочкой EX. Подключать термокабель необходимо через барьер искрозащиты ШСБ-ТК, устанавливаемый за пределами взрывоопасной зоны.

Модули МТС-х разработаны таким образом, что не требуют никакой настройки при запуске системы.

Подробнее
  • В линейке пороговых модулей МТС-x предусмотрено три исполнения:
    – МТС-1 – с возможностью подключения одного термошлейфа;
    – МТС-2 – с возможностью подключения двух термошлейфов;
    – МТС-3 – с возможностью подключения трех термошлейфов.

 

  • В зависимости от внешней оболочки применяемого термокабеля МТС-x может контролировать возгорание практически в любых условиях эксплуатации:
    – для уличного и внутреннего применения в обычных условиях эксплуатации при применении термокабеля с оболочкой из ПВХ, например, ИПТЛ-xxxС-PVC-ГРИФ-термокабель (где xxxС –температура срабатывания);
    – с агрессивной внешней средой и в условиях сурового климата при применении термокабеля с оболочкой из фторполимера, например, ИПТЛ-xxxС-CR-ГРИФ-термокабель (где xxxС –температура срабатывания);
    – во взрывоопасных зонах и на объектах с высокими электромагнитными помехами при применении термокабеля со специальной экранированной оболочкой, например, ИПТЛ-xxxС-EX-ГРИФ-термокабель (где xxxС –температура срабатывания).

 

  • Модули МТС-х рассчитаны на установку в необслуживаемых помещениях: степень защиты оболочки IP65 и рабочий диапазон температур -40°С до +55°C.
  • Возможность подключить к модулю МТС-х двухпороговые тепловые линейные пожарные извещатели позволяет существенно снизить риск запуска систем противопожарной защиты объекта вследствие повреждения (короткого замыкания) термокабеля.
  • Модули обеспечивают наглядную информацию о состоянии термошлейфов и самого прибора при помощи трёхцветных индикаторов.
  • Не требуют настройки и программирования.
Технические характеристики МТС-1 МТС-2 МТС-3
Количество термошлейфов 1 2 3
Допустимое удельное сопротивление термокабеля 0,05÷0,70 Ом/м
Длина термошлейфа 0÷3000 м (при 0,656 Ом/м)
0÷10000 м (при 0,19 Ом/м)
Сопротивление подводящих проводов не более 300 Ом
Контроль исправности шлейфов короткое замыкание / обрыв
Напряжение/ток питания шлейфов, не более 5,0 В/1,5 мА
Контроль вскрытия корпуса +
Выходы Пожар*, «сухой» перекидной контакт 1 2 3
Выход Авария*, «сухой» перекидной контакт +
Световая сигнализация Авария +
Питание +
Шлейф 1 + + +
Шлейф 2 + +
Шлейф 3 +
Электропитание (≤ 2,0 Вт) =11÷30,5 В
Средний срок службы не менее 10 лет
Диапазон рабочих температур от -40°C до +55°C
Допустимая относительная влажность до 93% при 40°C
Степень защиты оболочки IP65
Климатическое исполнение УХЛ 3.1
Масса не более 0,5 кг
Габариты, мм (ширина х высота х глубина) 160х160х60
* 125 VAC/0,5 A; 24 VDC/1 A