МС322-220 Модуль контроля и управления 4-канальный

WP_Post Object ( [ID] => 10060 [post_author] => 7 [post_date] => 2020-05-20 18:13:04 [post_date_gmt] => 2020-05-20 14:13:04 [post_content] => [post_title] => МС322-220 Модуль контроля и управления 4-канальный [post_excerpt] => [post_status] => publish [comment_status] => closed [ping_status] => closed [post_password] => [post_name] => ms322-220-modul-kontrolya-i-upravleniya-4-h-kanalnyj [to_ping] => [pinged] => [post_modified] => 2021-06-09 14:47:13 [post_modified_gmt] => 2021-06-09 10:47:13 [post_content_filtered] => [post_parent] => 0 [guid] => http://plazma-t.ru/?post_type=device&p=10060 [menu_order] => 0 [post_type] => device [post_mime_type] => [comment_count] => 0 [filter] => raw ) Array ( [_edit_lock] => Array ( [0] => 1623235519:116 ) [_edit_last] => Array ( [0] => 116 ) [slide_template] => Array ( [0] => default ) [type_pr] => Array ( [0] => 0 ) [_type_pr] => Array ( [0] => field_5dfb521bfd66b ) [short] => Array ( [0] => МС322-220 ) [description] => Array ( [0] => Модуль МС322-220 применяется в системах пожарной сигнализации и предназначен для:
  • контроля двух сигнальных входов НЗК/НРК с контролем на обрыв и КЗ (занимают два адреса) и двух технологических входов (не имеют адреса),
  • управления двумя нереверсивными устройствами или одним реверсивным устройством по командам от прибора ПАС300 с контролем исправности цепей управления с питанием на 220 В AC.
) [advdesc] => Array ( [0] =>

Модуль МС322-220 обеспечивает:

  • контроль исправности на обрыв и короткое замыкание двух сигнальных и двух технологических нормально-замкнутых или нормально-разомкнутых входов типа «сухой контакт»;
  • подключение двух нереверсивных исполнительных устройств или одного реверсивного устройства питанием на 220 В с контролем исправности цепей управления на обрыв и короткое замыкание;
  • контроль состояния цепи может осуществляться как во включенном, так и в выключенном состоянии. Исходное состояние устройства, т.е. оповещателя (в дежурном режиме) выбирается программно в ПРО. Если в исходном состоянии выход включен, то МС322-220 контролирует цепь управления только на обрыв.

Контроль работоспособности обеспечивается на программном уровне (постоянный опрос ПАС300).

Модуль занимает 4 адреса в адресном пространстве С300. Интерфейсная часть модуля питается от прибора ПАС300.

Электронное программирование адреса (заводская установка - 0).

Восемь встроенных трехцветных светодиодных индикаторов обеспечивают расширенную индикацию как состояний самого модуля (неисправность, дублирование адресов, нулевой адрес, нет в базе ПАС300 и т.д.), помимо состояний «Сработка» и «Дежурный режим», так и состояний подключенного оборудования, что значительно упрощает процессы настройки и обслуживания системы С300 в целом.

Предусмотрена возможность тестирования модуля при настройке и тестировании системы при помощи кнопки, находящейся внутри корпуса. При этом адрес модуля автоматически отобразится на Центральных приборах индикации (ЦПИ-Light/Pro).

Программирование параметров модуля МС322-220 осуществляется при помощи программы ПРО.

Каждый адресный вход можно установить в любую из 40 зон контроля в ПАС300 (по умолчанию зона 1).

Типы пожарных шлейфов доступны только при использовании нереверсивных устройств.

Для шлейфов типа НЗК и НРК предусмотрена возможность программирования типа сигнала, который будет формироваться в системе С300 при срабатывании входа (Пожар1, Пожар2, Внимание, Авария, нет сигнала).

Для каждого нереверсивного устройства, помимо включения/отключения и возможности задания задержки пуска и остановки, предусмотрена возможность контролировать выход устройства на режим (поле «Адрес» подтверждающего датчика), а также опции по контролю цепи до устройства (контроль на обрыв, контроль на КЗ, контроль на обрыв и КЗ, не контролировать).

При выборе нереверсивного устройства имеется возможность выбрать исходное состояние выхода в дежурном режиме:

  • при выключенной инверсии выход выключен;
  • при включенной инверсии выход включен.

Для реверсивного устройства входы модуля используются только для контроля положения устройства или могут быть отключены. Тип шлейфа при этом может быть выбран только как НЗК и НРК с возможностью программирования типа сигнала, который будет формироваться в системе С300 при срабатывании входа (Пожар1, Пожар2, Внимание, Авария, нет сигнала).

Для реверсивного устройства, помимо возможности задания задержки пуска и остановки, предусмотрена возможность выбора дежурного состояния (Реверсивный нормально открытый, Реверсивный нормально закрытый), а также опции по контролю цепи до устройства (контроль на обрыв, контроль на КЗ, контроль на обрыв и КЗ, не контролировать).

Для каждого устройства можно запрограммировать следующие команды:

  • «Пуск», «ПускУ12» - включение устройства по истечении времени задержки на пуск,
  • «½ Пуск» - включение устройства при поступлении двух и более команд «½ Пуск»,
  • «Пуск с блокировкой» - включение устройства, если отсутствует сигнал блокировки,
  • «Стоп» - выключение устройства по истечении времени задержки на останов,
  • «½ Стоп» - выключение устройства при поступлении двух и более команд «½ Стоп»,
  • «Отключить автоматику» - перевод устройства в режим «Автоматика устройства отключена»,
  • «Включить автоматику» - отключение режима «Автоматика устройства отключена».

В качестве условий для формирования команд может использоваться срабатывание:

  • В любой из 40 зон данного ПАС300 или любого из 24 приборов ПАС300, объединённых в сеть;
  • Любого шлейфа любого из приборов управления ПУ/ПУМ/ПУ-PL, объединённых в сеть;
  • В любой из 64 групп ЦПИ, в каждую из которых можно добавлять зоны ПАС300 и/или шлейфы ПУ/ПУМ/ПУ-PL.
Гарантийный срок составляет 84* месяца с момента выпуска, указанного в паспорте.

* На изделия, выпущенные с 01.06.2021г. Читать полные гарантийные обязательства.

) [tth] => Array ( [0] => ) [_pods_razdel] => Array ( [0] => 12 ) [numorder] => Array ( [0] => 5 ) [tth_tabl] => Array ( [0] =>
Технические характеристики
Сигнальные входы Количество 2
Напряжение входов 3,3 В
Контроль исправности на обрыв и короткое замыкание
Максимальная длина линии 100 м
Назначение входов формирование сигналов: - сигнализации (Пожар, Внимание, Авария) - управления (Управление1, Управление2)
Технологические входы Количество 2
Напряжение входов 3,3 В
Контроль исправности на обрыв и короткое замыкание
Максимальная длина линии 100 м
Назначение входов - авария питания; - авария устройства 1 или 2; - вкл/откл автоматику устройства 1 или 2; - ручной пуск/стоп устройства 1 или 2.
Устройства Количество управляемых устройств 2 независимых или 1 реверсивное
Напряжение для устройств равно напряжению электропитания модуля
Ток контроля нагрузки 1 мА
Максимальная мощность каждого выхода 100 ВА
Контроль исправности цепей на обрыв во всех состояниях и КЗ в дежурном режиме
Ток контроля исправности цепей не более 1,0 мА
Сопротивление цепи управления не более 300 Ом
Электропитание модуля 2 входа: ≈ 170 ÷ 245 В, 50/60 Гц, не более 2 ВА (собственное потребление модуля)
Интерфейс С300 Электропитание интерфейсной части от ПАС300 по интерфейсу С300
Напряжение интерфейса С300 от 11,5 до 28,0 В
Количество адресов в протоколе С300 4
Потребляемый ток от интерфейса не более 1,0 мА
Гальваническая развязка интерфейса есть
Изолятор короткого замыкания есть
Корпус Цвет корпуса светло-серый (RAL9002)
Масса, грамм не более 190
Габариты (ШхВхГ) 156х107х33 мм
Степень защиты оболочкой IP20
Крепление На саморезы или на DIN-рейку
Диапазон рабочих температур от -40 до +60°С
Допустимая относительная влажность до 93% при +40°С
Температура транспортировки и хранения от -50 до +50°С
Средний срок службы не менее 10 лет
Датчик вскрытия корпуса есть
) [hide_tech] => Array ( [0] => 0 ) [hide_down] => Array ( [0] => 0 ) [razdel_adr] => Array ( [0] => device ) [contact_form_code] => Array ( [0] => ) [_pods_devicedocs] => Array ( [0] => a:14:{i:0;i:10153;i:1;i:10154;i:2;i:3697;i:3;i:7592;i:4;i:7527;i:5;i:8922;i:6;i:3245;i:7;i:3308;i:8;i:9696;i:9;i:10753;i:10;i:5420;i:11;i:11612;i:12;i:11737;i:13;i:11752;} ) [_pods_images] => Array ( [0] => a:1:{i:0;i:10529;} ) [_relevanssi_pin] => Array ( [0] => ) [_relevanssi_unpin] => Array ( [0] => ) [razdel] => Array ( [0] => 12 ) [images] => Array ( [0] => 10529 ) [devicedocs] => Array ( [0] => 10153 [1] => 10154 [2] => 3697 [3] => 7592 [4] => 7527 [5] => 8922 [6] => 3245 [7] => 3308 [8] => 9696 [9] => 10753 [10] => 5420 [11] => 11612 [12] => 11737 [13] => 11752 ) )


смотреть все изображения

МС322-220
МС322-220 Модуль контроля и управления 4-канальный

Модуль МС322-220 применяется в системах пожарной сигнализации и предназначен для:

  • контроля двух сигнальных входов НЗК/НРК с контролем на обрыв и КЗ (занимают два адреса) и двух технологических входов (не имеют адреса),
  • управления двумя нереверсивными устройствами или одним реверсивным устройством по командам от прибора ПАС300 с контролем исправности цепей управления с питанием на 220 В AC.
Подробнее

Модуль МС322-220 обеспечивает:

  • контроль исправности на обрыв и короткое замыкание двух сигнальных и двух технологических нормально-замкнутых или нормально-разомкнутых входов типа «сухой контакт»;
  • подключение двух нереверсивных исполнительных устройств или одного реверсивного устройства питанием на 220 В с контролем исправности цепей управления на обрыв и короткое замыкание;
  • контроль состояния цепи может осуществляться как во включенном, так и в выключенном состоянии. Исходное состояние устройства, т.е. оповещателя (в дежурном режиме) выбирается программно в ПРО. Если в исходном состоянии выход включен, то МС322-220 контролирует цепь управления только на обрыв.

Контроль работоспособности обеспечивается на программном уровне (постоянный опрос ПАС300).

Модуль занимает 4 адреса в адресном пространстве С300. Интерфейсная часть модуля питается от прибора ПАС300.

Электронное программирование адреса (заводская установка – 0).

Восемь встроенных трехцветных светодиодных индикаторов обеспечивают расширенную индикацию как состояний самого модуля (неисправность, дублирование адресов, нулевой адрес, нет в базе ПАС300 и т.д.), помимо состояний «Сработка» и «Дежурный режим», так и состояний подключенного оборудования, что значительно упрощает процессы настройки и обслуживания системы С300 в целом.

Предусмотрена возможность тестирования модуля при настройке и тестировании системы при помощи кнопки, находящейся внутри корпуса. При этом адрес модуля автоматически отобразится на Центральных приборах индикации (ЦПИ-Light/Pro).

Программирование параметров модуля МС322-220 осуществляется при помощи программы ПРО.

Каждый адресный вход можно установить в любую из 40 зон контроля в ПАС300 (по умолчанию зона 1).

Типы пожарных шлейфов доступны только при использовании нереверсивных устройств.

Для шлейфов типа НЗК и НРК предусмотрена возможность программирования типа сигнала, который будет формироваться в системе С300 при срабатывании входа (Пожар1, Пожар2, Внимание, Авария, нет сигнала).

Для каждого нереверсивного устройства, помимо включения/отключения и возможности задания задержки пуска и остановки, предусмотрена возможность контролировать выход устройства на режим (поле «Адрес» подтверждающего датчика), а также опции по контролю цепи до устройства (контроль на обрыв, контроль на КЗ, контроль на обрыв и КЗ, не контролировать).

При выборе нереверсивного устройства имеется возможность выбрать исходное состояние выхода в дежурном режиме:

  • при выключенной инверсии выход выключен;
  • при включенной инверсии выход включен.

Для реверсивного устройства входы модуля используются только для контроля положения устройства или могут быть отключены. Тип шлейфа при этом может быть выбран только как НЗК и НРК с возможностью программирования типа сигнала, который будет формироваться в системе С300 при срабатывании входа (Пожар1, Пожар2, Внимание, Авария, нет сигнала).

Для реверсивного устройства, помимо возможности задания задержки пуска и остановки, предусмотрена возможность выбора дежурного состояния (Реверсивный нормально открытый, Реверсивный нормально закрытый), а также опции по контролю цепи до устройства (контроль на обрыв, контроль на КЗ, контроль на обрыв и КЗ, не контролировать).

Для каждого устройства можно запрограммировать следующие команды:

  • «Пуск», «ПускУ12» – включение устройства по истечении времени задержки на пуск,
  • «½ Пуск» – включение устройства при поступлении двух и более команд «½ Пуск»,
  • «Пуск с блокировкой» – включение устройства, если отсутствует сигнал блокировки,
  • «Стоп» – выключение устройства по истечении времени задержки на останов,
  • «½ Стоп» – выключение устройства при поступлении двух и более команд «½ Стоп»,
  • «Отключить автоматику» – перевод устройства в режим «Автоматика устройства отключена»,
  • «Включить автоматику» – отключение режима «Автоматика устройства отключена».

В качестве условий для формирования команд может использоваться срабатывание:

  • В любой из 40 зон данного ПАС300 или любого из 24 приборов ПАС300, объединённых в сеть;
  • Любого шлейфа любого из приборов управления ПУ/ПУМ/ПУ-PL, объединённых в сеть;
  • В любой из 64 групп ЦПИ, в каждую из которых можно добавлять зоны ПАС300 и/или шлейфы ПУ/ПУМ/ПУ-PL.

Гарантийный срок составляет 84* месяца с момента выпуска, указанного в паспорте.

* На изделия, выпущенные с 01.06.2021г. Читать полные гарантийные обязательства.

Технические характеристики
Сигнальные входы Количество 2
Напряжение входов 3,3 В
Контроль исправности на обрыв и короткое замыкание
Максимальная длина линии 100 м
Назначение входов формирование сигналов:
– сигнализации (Пожар, Внимание, Авария)
– управления (Управление1, Управление2)
Технологические входы Количество 2
Напряжение входов 3,3 В
Контроль исправности на обрыв и короткое замыкание
Максимальная длина линии 100 м
Назначение входов – авария питания;
– авария устройства 1 или 2;
– вкл/откл автоматику устройства 1 или 2;
– ручной пуск/стоп устройства 1 или 2.
Устройства Количество управляемых устройств 2 независимых или 1 реверсивное
Напряжение для устройств равно напряжению электропитания модуля
Ток контроля нагрузки 1 мА
Максимальная мощность каждого выхода 100 ВА
Контроль исправности цепей на обрыв во всех состояниях и КЗ в дежурном режиме
Ток контроля исправности цепей не более 1,0 мА
Сопротивление цепи управления не более 300 Ом
Электропитание модуля 2 входа: ≈ 170 ÷ 245 В, 50/60 Гц,
не более 2 ВА (собственное потребление модуля)
Интерфейс С300 Электропитание интерфейсной части от ПАС300 по интерфейсу С300
Напряжение интерфейса С300 от 11,5 до 28,0 В
Количество адресов в протоколе С300 4
Потребляемый ток от интерфейса не более 1,0 мА
Гальваническая развязка интерфейса есть
Изолятор короткого замыкания есть
Корпус Цвет корпуса светло-серый (RAL9002)
Масса, грамм не более 190
Габариты (ШхВхГ) 156х107х33 мм
Степень защиты оболочкой IP20
Крепление На саморезы или на DIN-рейку
Диапазон рабочих температур от -40 до +60°С
Допустимая относительная влажность до 93% при +40°С
Температура транспортировки и хранения от -50 до +50°С
Средний срок службы не менее 10 лет
Датчик вскрытия корпуса есть


Поиск документов